Rapid Shutdown
Rapid shutdown lets firefighters quickly lower the voltage in the solar wiring on a building. Section 690.12 of the National Electrical Code (NEC) says PV system circuits installed on or in buildings "shall include a rapid shutdown function to reduce shock hazard for firefighters." Many rooftop string-inverter arrays meet it with small shutdown devices in the array that stay on only while a transmitter or the inverter tells them to. Choose parts by the rapid shutdown system your inverter uses: Tigo, APsmart or Tesla.
Read more about Rapid Shutdown
- Tigo Fire Safety: the Tigo TS4-A-F serves one panel and the Tigo TS4-A-2F serves two. They need a Tigo RSS transmitter, such as the single-core outdoor kit (492-00000-51) or the Tigo RSS Transmitter (492-00000-52), unless your inverter has a built-in Tigo certified transmitter.
- APsmart (SunSpec signal): APsmart RSD-S-PLC module devices (15A) with the APsmart Transmitter-PLC Outdoor Kit (408006), or with an inverter that has an integrated SunSpec-certified transmitter. For a shutdown button, see the BG10P34-11 emergency stop station.
- Tesla Solar Inverter: Tesla MCI-2 High Current (15A) mid-circuit interrupters, installed inside the PV strings. Turning off the PV system AC breaker or disconnect starts shutdown.
- Tigo monitoring systems (TS4-O and TS4-S): the Tigo Cloud Connect Advanced (CCA) Outdoor Kit includes a Tigo Access Point (TAP) and a DIN-rail power supply. Tigo says the CCA paired with a TAP enables NEC 690.12 compliance for those TS4 units.
Using Enphase IQ8 microinverters? Enphase lists its residential IQ8 models and the commercial IQ8P-3P as UL Listed PV rapid shutdown equipment when installed according to its instructions, so they usually do not need the add-on devices on this page. See microinverters. Want help with a full parts list? Request a written quote.
- TigoSKUTS4-A-F$44.78Available to order Shipping calculated at checkout
- TigoSKUTS4-A-2F
Tigo TS4-A-2F Module-Level Fire Safety with Rapid Shutdown, 2.2m MC4 Cables
$63.66Available to order Shipping calculated at checkout - TigoSKU492-00000-52
Tigo RSS Transmitter PV Rapid Shutdown Transmitter
$55.55Available to order Shipping calculated at checkout - Tigo
- APsmartSKUAPSM-RSD-S-PLC-415
APsmart RSD-S-PLC Module-Level Rapid Shutdown Device, 15A
$37.25Available to order Shipping calculated at checkout - APsmartSKU408006
APsmart Transmitter-PLC Outdoor Kit, Single Core, 85–264VAC Power Supply – 408006
$250.53Available to order Shipping calculated at checkout - APsmartSKUBG10P34-11
APsmart Rapid Shutdown Initiator Switch – BG10P34-11
$95.02Available to order Shipping calculated at checkout - TeslaSKUMCI-2 15A
Tesla MCI-2 High Current Mid-Circuit Interrupter, 15A Rapid Shutdown Device
$63.83Available to order Shipping calculated at checkout - TigoSKU492-00000-51
Tigo RSS Transmitter Kit, Single Core, DIN Rail, Outdoor – 492-00000-51
$227.25Available to order Shipping calculated at checkout
How rapid shutdown works
Tigo TS4-A-F and TS4-A-2F units used with a Tigo RSS Transmitter (or an inverter with a built-in Tigo certified transmitter), and APsmart RSD-S-PLC units, use a keep-alive signal over the PV wires. While the system runs, the transmitter sends that signal and the devices on the roof stay on while they receive it. When the transmitter loses power, the signal stops and the devices shut down. That happens when someone presses an emergency stop button wired to the transmitter's power or turns off its AC supply. Tigo says each TS4-A-F or TS4-A-2F then drops its output to 0.6 V, which keeps a string under 30 V. That PLC path and 0.6 V figure apply to the TS4-A-F/2F Fire Safety devices with an RSS Transmitter; they do not describe the Tigo Cloud Connect Advanced (CCA) and TAP route, which talks wirelessly to TS4-A-O and TS4-A-S devices.
Tesla works differently. Tesla lists the MCI-2's passive state as normally open, with power line excitation as its control. Tesla's datasheet says that when the MCI is paired with the Tesla Solar Inverter, array shutdown starts with any loss of AC power, such as turning off the PV system AC breaker or disconnect.
Residential Enphase IQ8 microinverters handle rapid shutdown at each panel when installed according to Enphase's instructions. On a grid-tied (interactive) system, Enphase says rapid shutdown may start from the PV system disconnect or the service disconnect. When those microinverters run with an IQ System Controller 2 for backup (multimode), Enphase requires a separate rapid shutdown initiator. The Enphase Power Kit with IQ System Controller 2 and Rapid Shutdown Switch includes that switch. A backup system with an IQ System Controller 3 or 3G uses Enphase's System Shutdown Switch as the rapid shutdown initiator. The commercial IQ8P-3P is also UL Listed as PV rapid shutdown equipment when installed according to Enphase's instructions; follow Enphase's commercial guide, which requires an accessible initiating device or a suitable automatic disconnect or emergency system, not the residential controller path.
Compare rapid shutdown systems
| System | Device in the array | What keeps it on | How shutdown starts | Key limits (per manufacturer) |
|---|---|---|---|---|
| Tigo TS4-A-F / TS4-A-2F | One unit per panel (TS4-A-F) or per two panels (TS4-A-2F) | Tigo RSS transmitter, or an inverter with a built-in Tigo certified transmitter | Transmitter loses power (emergency stop button or AC off) | 80 V max per input; shutdown in under 30 seconds. RSS core: up to 10 strings, 30 panels per string, 160 A, 1500 VDC |
| APsmart RSD-S-PLC | Module-level device | APsmart Transmitter-PLC, or an inverter with an integrated SunSpec-certified transmitter | Transmitter is switched off | 10.5–80 V input; 15 A continuous (this listing); 25 A short-circuit current. Outdoor kit core: up to 30 panels per string; 10–15 strings per core depending on cable size |
| Tesla MCI-2 High Current | Mid-circuit interrupter inside each string | Tesla Solar Inverter | Loss of AC power, such as the PV system AC breaker or disconnect turned off | 15 A Imp / 19 A Isc; 165 V per MCI when open; up to 5 per string; system voltage limited to 600 VDC by the Tesla Solar Inverter |
Numbers come from each manufacturer's current datasheet. Check the exact part number and full limits on each product page before you design.
How to choose rapid shutdown parts
- Start with your inverter or charge controller. Its datasheet tells you whether it has a built-in rapid shutdown transmitter and which signal it uses. If it has one, you add matching roof devices and skip the separate transmitter. For example, we list the Solis S6 16kW hybrid with a built-in APsmart rapid shutdown transmitter.
- Keep one signaling system. Tigo TS4-A-F and TS4-A-2F units go with a Tigo RSS transmitter. APsmart RSD-S-PLC units go with an APsmart Transmitter-PLC or an integrated SunSpec-certified transmitter. Do not mix brands unless the manufacturer's compatibility list includes that pairing.
- Count the devices. Plan one TS4-A-F per panel or one TS4-A-2F per two panels. For Tesla, the number and placement of MCIs follow Tesla's UL 3741 Application Addendum for your array type.
- Check the electrical limits. Your panel's current and voltage must stay within the device ratings, and the strings that pass through a transmitter core must stay within its string and panel counts.
- Plan the shutdown switch and labels. APsmart shows an optional emergency stop button that disconnects the transmitter's AC power. The NEC also has labeling rules for rapid shutdown. The PV Labels 2023 NEC Value Pack (05-523) and 2020 NEC Value Pack (05-520) are sorted by code edition, and PV Labels says they cover rapid shutdown equipment.
- Confirm your code edition and inspector. Your local inspector (the authority having jurisdiction, or AHJ) and the NEC edition your area has adopted decide which rapid shutdown method is accepted.
Our articles NEC 690.12 rapid shutdown, part 1: inverters and part 2: charge controllers walk through how the rules developed and the options for grid-tie and battery-based systems.
What else you may need
- Usually required, a transmitter or a built-in one: roof devices do not work alone. Use the matching transmitter kit above, or an inverter with a built-in transmitter for the same signal. Compare inverters on hybrid inverters.
- Usually required, a way to start shutdown: an emergency stop button such as the BG10P34-11, or the AC disconnect your system design uses. See disconnects and breakers.
- May be required, an outdoor enclosure: Tigo rates bare RSS transmitters NEMA 1 (indoor). Both Tigo RSS kits listed here include Tigo's outdoor enclosure, rated IP67 and NEMA 3R.
- May be required, labels: PV label packs for the 2023 NEC or 2020 NEC.
- Optional, monitoring: Tigo and Enphase monitoring and control equipment is on monitoring and control.
Rapid shutdown FAQ
What does NEC 690.12 require?
It says PV system circuits installed on or in buildings shall include a rapid shutdown function to reduce shock hazard for firefighters. The detailed limits depend on the NEC edition your area has adopted, so confirm the method with your local inspector before you buy parts.
Does the Tigo TS4-A-F need a transmitter?
Yes. Tigo says the TS4-A-F meets NEC 690.12 when installed with the Tigo RSS Transmitter or an inverter with a built-in Tigo certified transmitter. The same is true for the TS4-A-2F.
How is rapid shutdown started?
In Tigo TS4-A-F and TS4-A-2F systems with an RSS Transmitter, and in APsmart systems, removing power from the transmitter stops the keep-alive signal over the PV wires and the roof devices shut down. That can be an emergency stop button wired to the transmitter's power or turning off its AC supply. The Tigo CCA and TAP route talks wirelessly to TS4-A-O and TS4-A-S devices; it does not use that PLC keep-alive path. Tesla MCI-2 devices open when AC power to the Tesla Solar Inverter is lost, such as when the PV system AC breaker or disconnect is turned off.
Do Enphase microinverters need separate rapid shutdown devices?
Usually not. Enphase lists its residential IQ8 microinverters and the commercial IQ8P-3P as UL Listed PV rapid shutdown equipment when installed according to its instructions. Initiation depends on the system. On a grid-tied (interactive) residential IQ8 system, Enphase says rapid shutdown may start from the PV system disconnect or the service disconnect. A residential backup system with an IQ System Controller 2 in multimode needs Enphase's rapid shutdown initiator. A system with an IQ System Controller 3 or 3G uses the System Shutdown Switch. The commercial IQ8P-3P follows Enphase's commercial initiating-device instructions, not the residential controller path.
Can I mix Tigo and APsmart rapid shutdown parts?
Plan on one system. Tigo TS4-F units listen for a Tigo RSS signal, and APsmart RSD units listen for the APsmart or SunSpec-certified transmitter signal. Mix brands only when the manufacturer's current compatibility list includes that exact pairing.
Do ground-mounted arrays and carports need rapid shutdown?
Not always. Under the 2023 NEC, the exceptions cover ground-mounted PV circuits that enter buildings whose sole purpose is to house PV equipment, and PV equipment on nonenclosed detached structures such as carports, parking shade structures and solar trellises. Earlier editions are worded differently, so check the edition your area uses and ask your inspector.