SPECIFICATIONS
|
| Input Power |
2Watts @ 120 VDC |
| Relay Contact Ratings: |
#832 UL #E88991, CSA #1429333
Common (CM)-
30VDC MAX. or 250VAC MAX.
Normally Open (NO)-
20A resistive @ 120VAC & 250VAC
1 HP @ 120VAC; 2 HP @ 250VAC
20A @ 30VDC; TV-5
Normally Closed (NC)-
20A resistive @ 120VAC & 250VAC
1/4 HP @ 120VAC; 1/2 HP @ 250VAC
15A @ 30VDC |
| Differential: |
Adjustable 8° to 24°F; fixed 4°F reset |
| High Limit: |
Adjustable from 110° to 200°F |
| Accuracy: |
+/- 1 °F |
| Environmental: |
-10 to 120 °F
0 to 95% RH |
| Temperature Sensors: |
10K @ 25°C/77°F Rated to 400°F |
| Dimensions: |
5”W x 6 ”H x 2.5”deep |
TEMPERATURE DIFFERENCE CONTROL
When the temperature difference between the sensor on the
solar collector and the sensor in the storage tank exceeds the dialed temperature difference setting (ON DIF),
the pump relay will actuate after a 30 second delay. The blue LED indicator will also turn ON. When the
temperature difference decreases and falls below 4 F (2.2 C), the pump relay and the blue LED indicator will
turn off without delay.
HIGH LIMIT CONTROL- When the temperature in the storage tank exceeds the HI-LIMIT dialed setting, the
PUMP relay will be turned OFF without delay regardless of the status of the temperature difference that exists
between the storage tank and the solar collector. The blue LED indicator will also turn OFF. When
the storage tank temperature falls 4 degrees below the setting in the HI-LIMT, the controller will then resume
normal operation. The pump relay will always have a 30 second delay before switching ON and the blue LED
will always show its STATUS condition.
LOW TEMPERATURE SHUT DOWN
This feature is available to prevent the system from operating at
low outdoor temperatures. If this feature is enabled normal operation will stop when the collector temperature
falls below 50 degrees F. The
pump relay will then be turned off. Normal control operation will not resume until
the collector temperature returns to 70 degrees or above. To enable this feature, a jumper must be placed onto the jumper pins marked "LO" on the circuit board.
Only ONE of these two override features can be enabled.
FREEZE PROTECTION OVERRIDE
This feature is available to prevent a non-drain back "water only" system
from freezing when the outdoor temperature drops too low. If this feature is enabled normal operation will stop
when the collector temperature falls below 37 F. The pump relay will then be turned ON until the
collector temperature reaches 52 F. Normal control operation will resume above this temperature. To
enable this feature, a jumper must be placed onto the jumper pins marked “FZ’ on the circuit board. Only ONE
of these two override features can be enabled.
STATUS INDICATION LEDS There are four status indication LEDS. The GREEN LED indicates that the
microprocessor is powered and the solar controller is running. The BLUE LED indicates pump operation.
When ON, the pump is operating and solar energy is being stored in the storage tank. The AMBER LED
indicates if the UPPER LIMIT temperature in the storage has been exceeded. The RED LED indicates when
there is a fault condition. The conditions that can cause the fault LED to turn ON are as follows: OPEN or
SHORTED or OUT of RANGE temperature sensors, pump relay switch not set to “AUT” (automatic)
position and internal component malfunctions. The RED LED will always be flashing when the FAULT
indication is ON.
SENSORS
Industrial 400°F (204°C) rated 10K IMC thermistors have +/- 1°F accuracy. When installed, they
will not exceed ONE degree of additional error for cable distances up to 1000 feet of 18ga., 700 feet of 20ga. or
500 feet of 22ga.
SENSOR SCREW TERMINALS
There are 9 screws on a GREEN block located at the top edge of the board.
These terminals accept solid or stranded wire from 18ga. to 22ga. They are NEC class 2 circuit connections.
POWER AND RELAY TERMINALS
This model operates on 12 vdc @ 2 watts. Operation outside 10 vdc to
15 vdc is not guaranteed and operation above 15 vdc will void warranty. The relay is UL & CSA rated for 20
amps resistive load on the normally open (N.O.) contacts and can be used to power pumps or FANS directly
not exceeding a total of 1 hp. The “normally closed” contacts are rated for 10 amps resistive or a maximum of
1/4 hp. For D.C. operation, the relay is UL & CSA rated for 20 amps at 30 volts on the normally open (N.O.)
contacts and 15 amps on the normally closed (N.C.) Contacts.

See more technical information and installation instructions about this differential temperature control in the Product Documentation section above! |