INTEGRATED PV INVERTER
The Solectria Renewables PVI 60KW, PVI82KW and PVI95KW are rugged, DSP-controlled premium efficient PV inverters for grid-connected commercial, industrial and utility 3-phase PV systems. The core of the inverter, a 600VCD version of Solectria's proven DMGI 660 distributed generation inverter, uses state of the art control techniques and devices including space vector PWM, a precision MPT algorithm, and low-loss IGBTs. With peak inverter power electronics efficiency over 98% (over 96% including the transformer and filters) and fully integrated packaging, these inverters set a new industry standard for efficiency, ease of installation and use, reliability and installed cost.
CONNECTIVITY
- RS232 and PC software for diagnostics and data capture
- RS485 option for communication with multiple inverters in larger systems, or with long communication lines.
- Fat Spaniel Inverter-Direct Internet or cellular data monitoring option.
SAFETY FEATURES
The PVI 60KW, 82KW AND 95KW inverters include electronic temperature protection, DC ground-fault detection and interrupt, current limit protections and standards compliance: All inverters listed to UL 1741 and IEEE Std 1547 and certified to IEEE 62.41 (NY SIR Surge Test Requirements). Units are also listed on CEC's eligible equipment list.
SPECIFICATIONS
|
PVI 60KW |
PVI 82KW |
PVI 95KW |
Output |
Continuous AC Power (CEC) |
60 kW |
83 kW |
95 kW |
Power Factor |
> 0.98 |
Voltage (L-L), ±10% |
208 / 480 VAC, 3-Ph |
Rated Current 208VAC
(&CEC rated current) 480VAC |
166A
73A |
229A
100A |
261A
115A |
Current Distortion |
< 5% THD, Nom Power |
Frequency, ±1 % |
60 Hz |
Inverter Electronics Peak Efficiency |
> 98% (50%-100% load) |
Overall Peak Efficiency 1 |
> 96% (50%-100% load) |
| Input |
Array Configuration: |
Monopole, negative grounded
(Positive ground option) |
Max VOC 2 |
600 VDC |
Maximum DC Current |
190A |
248A |
287A |
CEC Eligible DC Current |
177A |
241A |
279A |
MPT Voltage Range |
330-500 VDC |
CEC Full Power Voltage Range |
346-480 VDC |
Protection 3 |
AC Grid-connection
(Standards Compliance: See
“Safety Features”) |
Over/Under Voltage, Over Current
Over/Under Freq.,
DC Ground Fault (GFDI) |
AC Disconnect (Integral) |
NEMA 3R, Integral |
DC Sub-Combiner w/Fuses
(Optional 4) |
40A-100A fuses available, 3-8 pole, NEMA 3R, TVSS |
DC Disconnect (Integral) |
Break load rated, NEMA 3R |
| Environmental |
Ambient Temperature |
-25 to 50 deg C (full power) |
Cooling |
Automatic Forced Convection |
Enclosure |
Rain Proof (UL 1741) |
Electronics Enclosure |
Sealed (IP62) |
| General |
Weight lb (kg) |
1526 (694) |
1591 (713) |
1610 (732) |
Dimensions: inch [mm] 208VAC
(Height w/o lifting eyes) 480VAC |
76[1930] H x 56[1422] W x 29.3[744] D
76[1930] H x 54[1372] W x 25.3[643] D |
Communications, Optional Data Acquisition |
RS232, RS485, PVIDAQ PC software,
Fat Spaniel Inverter-Direct Option |
Warranty |
5 years standard
(optional 10 & 15 year warranties) |
1 Fully Integrated Package: Includes premium efficient transformer, filters, brushless
blower, AC & DC disconnects. (>95.5% peak efficiency for 208VAC versions)
2 Max Open circuit voltage (VOC) of PV array = 1.25 x Voc rated (per NEC 690-7).
3 Complies with grid connection and safety standards (“Safety Features”)
4 Integrated into inverter package if selected. |
|