Log in | My Account | ![]()
Cart: 0 items
| List Price: | $1,920.00 |
| Our Price: | $1,459.00 Save: $461.00 (24%) |
| Model: | SB700U SBD |
| Brand: | SMA - America |
|
Our Code: SMASB700ULSBD |
|
Use the SMA America String Sizing Utility program to determine the size and configuration of your system. (Please read the disclaimer before using the sizing tool, and do not hesitate to contact the knowledgeable staff at The Alternative Energy Store with any questions you may have!) |
|
Input Values (250VDC)
|
||
|
Recommended max PV Power
|
PPV | 1000 Wp STC* |
|
Max DC Power
|
PDC, max | 700 Wp PTC** |
|
Max DC Voltage
|
VDC, max | 250 Vdc |
|
PV Voltage range, MPP
|
VPV | 123V to 250V |
|
Max input current
|
IPV, max | 7 A |
|
DC Voltage ripple
|
VPP | < 10% |
|
DC Disconnectors
|
Optional external DC Disconnect/Breaker | |
|
Pole confusion protection
|
Short Circuit diode | |
|
Ground fault protection
|
IDif | > 1000 mA |
|
Input Values (200VDC)
|
||
|
Recommended max PV Power
|
PPV | 840 Wp STC* |
|
Max DC Power
|
PDC, max | 600 Wp PTC** |
|
Max DC Voltage
|
VDC, max | 250 Vdc |
|
PV Voltage range, MPP
|
VPV | 100V to 200V |
|
Max input current
|
IPV, max | 7 A |
|
DC Voltage ripple
|
VPP | < 10% |
|
DC Disconnectors
|
Optional external DC Disconnect/Breaker | |
|
Pole confusion protection
|
Short Circuit diode | |
|
Ground fault protection
|
IDif | > 1000 mA |
|
Input Values (150VDC)
|
||
|
Recommended max PV Power
|
PPV | 640 Wp STC* |
|
Max DC Power
|
PDC, max | 460 Wp PTC** |
|
Max DC Voltage
|
VDC, max | 250 Vdc |
|
PV Voltage range, MPP
|
VPV | 77V to 150V |
|
Max input current
|
IPV, max | 7 A |
|
DC Voltage ripple
|
VPP | < 10% |
|
DC Disconnectors
|
Optional external DC Disconnect/Breaker | |
|
Pole confusion protection
|
Short Circuit diode | |
|
Ground fault protection
|
IDif | > 1000 mA |
|
Output Values (250VDC)
|
||
|
Max AC Power
|
PAC | 700 W |
|
Total Harmonic Distortion
|
THDIAC | < 4% (With KVgrid < 2% and PAC > 0.5 PACnom) |
|
Operating Range, Grid
Voltage
|
VAC | 106 V to 132 V |
|
Operating Range, Grid
Frequency
|
fAC | 59.3 Hz - 60.5 Hz |
|
Phase Shift (Ref. Fundamental)
|
cos(phi) | 0° |
|
Output Values (200VDC)
|
||
|
Max AC Power
|
PAC | 600 W |
|
Total Harmonic Distortion
|
THDIAC | < 4% (With KVgrid < 2% and PAC > 0.5 PACnom) |
|
Operating Range, Grid
Voltage
|
VAC | 106 V to 132 V |
|
Operating Range, Grid
Frequency
|
fAC | 59.3 Hz - 60.5 Hz |
|
Phase Shift (Ref. Fundamental)
|
cos(phi) | 0° |
|
Output Values (150VDC)
|
||
|
Max AC Power
|
PAC | 460 W |
|
Total Harmonic Distortion
|
THDIAC | < 4% (With KVgrid < 2% and PAC > 0.5 PACnom) |
|
Operating Range, Grid
Voltage
|
VAC | 106 V to 132 V |
|
Operating Range, Grid
Frequency
|
fAC | 59.3 Hz - 60.5 Hz |
|
Phase Shift (Ref. Fundamental)
|
cos(phi) | 0° |
|
Output Protection
|
||
|
Islanding Protection
|
VAC; fAC in accordance with UL 1741 | |
|
Ground Fault Protection
|
IDIF; In accordance with UL 1741 | |
|
AC Disconnect
|
External AC Breaker | |
|
Short Circuit Protection
|
Current Controlled | |
|
Overvoltage Classification
|
III |
|
Efficiency
|
||
| Peak Efficiency (250VDC) | 93.6 % (Rebate Efficiency) | |
| Peak Efficiency (200VDC) | 93.3 % (Rebate Efficiency) | |
| Peak Efficiency (150VDC) | 92.4 % (Rebate Efficiency) |
| Power Consumption | ||
| Internal consumption in operation | < 4 W | |
| Internal consumption at night | 0.1 W | |
| American Standards | ||
| Hardware Safety | UL 1741 | |
| Firmware Safely | UL 1998 | |
| Power Quality | IEEE 519 | |
| Anti-Islanding | IEEE 929 | |
| Surge Testing | ANSI C62.41, C1 & C3 | |
| Electro-Magnetic Interference | FCC Part 15 A & B | |
| Size and Weight | ||
| Width | 322 mm | |
| Height | 320 mm | |
| Depth | 180 mm | |
| Weight | ca. 16 kg | |
| Enclosure Ratings | ||
| DIN EN 60529 | IP 65 | |
| NEMA Rating | NEMA 4X | |
| Ambient Conditions | ||
| Ambient Temperature Range | -13ºF to +140ºF or -25ºC to +60ºC | |
| Relative Humidity Level | 0 to 100% |